Fault - 2 - Initializing

Cause-

  •  Inverter is waiting for driving signal


Solution-

  • Test – DC switch OFF
  • Check PV connections
  • Check polarity
  • Check voltage >120V Single, >350V three 
  • Test – DC Switch ON
  • Check voltage >120V Single, >350V three
  •  A cable may have been damaged or loosened in shipping replace inverter


Troubleshooting - Inverter is stuck on initializing. The inverter may not be receiving the signal from the DSP .  A faulty power board may cause this issue as well, so checking the components for faults or shorts may remedy this issue. 