Error Code 103 - High DC Input Voltage

Possible CauseSuggestion
Cause ID = 1 The PV array is not properly configured.Excessive PV modules are connected in series to PV strings 1 and 2, and therefore the PV string open-circuit voltage exceeds the inverter maximum MPP voltage.


Cause ID = 1 Reduce the number of PV modules connected in series to PV strings 1 and 2 until the open-circuit voltage is less than or equal to the maximum inverter input voltage. After the PV array configuration is corrected, the inverter alarm disappears.


Cause ID = 2 The PV array is not properly configured.Excessive PV modules are connected in series to PV strings 3 and 4, and therefore the PV string open-circuit voltage exceeds the inverter maximum MPP voltage.


Cause ID = 2 Reduce the number of PV modules connected in series to PV strings 3 and 4 until the open-circuit voltage is less than or equal to the maximum inverter input voltage. After the PV array configuration is corrected, the inverter alarm disappears.


Cause ID = 3 The PV array is not properly configured.


Cause ID = 3 Reduce the number of PV modules connected in series to PV strings 5 and 6 until the open-circuit voltage is less than