Warning - THM18

Display - Outlet Water Temp


Description-

Stacks’ Outlet Water Temperature sensor exceeds over-temperature threshold (72 °C)for 10 seconds.


Resolution-

Coolant is exceeding allowed temperature-rise thru IBGT stacks, prior to radiator


1. Verify Outlet Temp reading on HMI compared to IGBT temps: Monitor menu


■ Temperature 2 menu: M1A/B/C | M2A/B/C | M3A/B/C


■ Verify coolant Inlet Temp is within specification (sufficiently cooled)


2. Check coolant Temperature Sensor/Transducer TT2 in LC cabinet section: wiring


■ TB11-7 | TB11-14 | CANUX2 J7-10/5/(4-shield drain-wire)