Warning - OF

Display - Over-Frequency


Description-

Grid over-frequency alarm 


Frequency >101.6%Rated 


Frequency [60.96 Hz] for 1.2 sec


Resolution-

SEL set for UL1741 grid-tie parameters: incompatible with over-frequency ride-thru


■ Check for/if SCADA control seeking over-frequency ride-thru