Customer Solution Portal

Submit a ticket My Tickets
Welcome
Login  Sign up

Warning - IFS3

Display- Inverter 3 Fault (Software)


Description-

Instantaneous Module Over current on SIB board 110% of peak nominal value


(Nominal value = 1000 A)Trip level: 1550 A peak, 1100 A RMS


Resolution-

1. Check all ribbon cable connections. On SIB3


2. Fault reset on HMI, retry inverter

Did you find it helpful? Yes No

Send feedback
Sorry we couldn't be helpful. Help us improve this article with your feedback.