Warning - IF2

Display - Inverter 2 Current


Description-

Instantaneous Module Over current on SIB board 110% of peak nominal value(Nominal value = 1000 A)


Trip level: 1550 A peak, 1100 A RMS


Resolution-

1. Check all ribbon cable connections. On SIB2


2. Fault reset on HMI, retry inverter

Did you find it helpful? Yes No

Send feedback