Customer Solution Portal

Submit a ticket My Tickets
Welcome
Login  Sign up

Warning - GRF6

Display -  Grid C Voltage


Description-

Over-voltage protection of 125% of rated signal (Nominal value = 320/356 Vac)Trip level: 400/445 Vac > 1 msec


Resolution-

Inverter detecting over-voltage on its output


1. Check transformer taps for proper set-up ratio can indicate incorrect MV-transformer or mains’ transformer taps


2. Check inverter voltage-sense transformer TR1B wiring

Did you find it helpful? Yes No