Customer Solution Portal

Submit a ticket My Tickets
Welcome
Login  Sign up

Warning - GRF4

Display - Grid A Voltage


Description-

Over-voltage protection of 125% of rated signal(Nominal value = 320/356 Vac)Trip level: 400/445 Vac >1 msec


Resolution-

Inverter detecting over-voltage on its output


1. Check transformer taps for proper set-up ratio can indicate incorrect MV-transformer or mains’ transformer taps


2. Check inverter voltage-sense transformer TR1A wiring

Did you find it helpful? Yes No

Send feedback
Sorry we couldn't be helpful. Help us improve this article with your feedback.