Customer Solution Portal

Submit a ticket My Tickets
Welcome
Login  Sign up

Warning - GRF1

Display - Grid A Overcurrent


Description-

Over-current protection of 115% rated feedback. (Nominal value = 2706 A)Trip level: 3112 A >1 msec


Resolution-

Inverter sourcing too much current into the transformer/grid


1. Check transformer taps for proper set-up ratio can indicateincorrect MV-transformer or mains’ transformer taps


2. Check inverter current-transformer CTA wiring

Did you find it helpful? Yes No

Send feedback
Sorry we couldn't be helpful. Help us improve this article with your feedback.